TFR-CVV 3x10mm²
Description
Description
Standards
-
NationalKS C IEC 60502-1; KWS 411
Application
Power cable for residential, commercial building and distribution circuit.
The flame retardant cable for tray conformed to the standard of technique of electrical equipment.
Standard
K 60502-1
KWS 411: 0.6/1kV Flame retardant control cable
Construction
1. Conductor: Stranded annealed round plain copper, Class 2
2. Insulation: PVC, operating temperature 70°C.
3. Unit: Cabling circularly insulated solid wire in case of more than 2 cores
4. Outer sheath: Black flame retardant black PVC (TFR PVC)
Colors
2 cores: White /Black
3 cores: White / Black /Red,
4 cores: White / Black / Red / Green
More 5 cores: Numbering on black or red core. The others are white
Certification
KETI
KWS (Collective standard)
TFR-CVV 0.6/1kV design
##image:55999## |
Insulation Filler Binder tape Outer sheath (TPR PVC)
|
The values of insulation resistance is not defined but only constant number of insulation resistance is defined
(K=min. 36.7MΩ.km at room temperature, min. 0.037MΩ.km at 70℃)
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Dimensional characteristics
Dimensional characteristics
Electrical characteristics
Electrical characteristics
Usage characteristics
Usage characteristics
Resources
Resources
Current capacity table PVC insulation multicore single phase
PVC insulation/two loaded conductors, copper or aluminium – Conductor temperature: 70 °C, ambient temperature: 30 °C in air, 20 °C in groundConductor cross-section | ||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
10.0 | 46.0 | 36.0 | 43.0 | 33.0 | 52.0 | 41.0 | 63.0 | 49.0 | 60.0 | 47.0 | 64.0 | 0.0 | 70.0 | 54.0 |
A1 Insulated conductors in conduit in a thermally insulated wall |
A2 Multi-core cable in conduit in a thermally insulated wall |
B2 Multi-core cable in conduit on a wooden wall |
C Single-core or multi-core cable on a wooden wall |
D1 Multi-core cable in ducts in the ground |
D2 Multi-core cables designed to be buried directly in the ground |
E Multi-core cable in free air |
Current capacity table PVC insulation multicore three phase
PVC insulation, three loaded conductors/copper or aluminium – Conductor temperature: 70 °C, ambient temperature: 30 °C in air, 20 °C in groundConductor cross-section | ||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
10.0 | 42.0 | 32.0 | 39.0 | 31.0 | 46.0 | 36.0 | 57.0 | 44.0 | 50.0 | 39.0 | 54.0 | 0.0 | 60.0 | 46.0 |
A1 Insulated conductors in conduit in a thermally insulated wall |
A2 Multi-core cable in conduit in a thermally insulated wall |
B2 Multi-core cable in conduit on a wooden wall |
C Single-core or multi-core cable on a wooden wall |
D1 Multi-core cable in ducts in the ground |
D2 Multi-core cables designed to be buried directly in the ground |
E Multi-core cable in free air |
Current capacity table PVC insulation single core single phase
PVC insulation/two loaded conductors, copper or aluminium – Conductor temperature: 70 °C, ambient temperature: 30 °C in air, 20 °C in groundConductor cross-section | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
10.0 | 46.0 | 36.0 | 57.0 | 44.0 | 63.0 | 49.0 | 60.0 | 47.0 | 64.0 | 0.0 | 0.0 | 0.0 |
A1 Insulated conductors in conduit in a thermally insulated wall |
B1 Insulated conductors in conduit on a wooden wall |
C Single-core or multi-core cable on a wooden wall |
D1 Single core or Multi-core cable in ducts in the ground |
D2 Single core or Multi-core cables designed to be buried directly in the ground |
F Single-core flat cables, touching in free air |
Current capacity table PVC insulation single core three phase
PVC insulation, three loaded conductors/copper or aluminium – Conductor temperature: 70 °C, ambient temperature: 30 °C in air, 20 °C in groundConductor cross-section | ||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
10.0 | 42.0 | 32.0 | 50.0 | 39.0 | 57.0 | 44.0 | 50.0 | 39.0 | 54.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 |
A1 Insulated conductors in conduit in a thermally insulated wall |
B1 Insulated conductors in conduit on a wooden wall |
C Single-core or multi-core cable on a wooden wall |
D1 Single core or Multi-core cable in ducts in the ground |
D2 Single core or Multi-core cables designed to be buried directly in the ground |
F Single-core flat cables, touching in free air |
Ft Single-core trefoil cables, touching in free air |