TFR-CV 3x 240mm²

Description

Description

Standards

  • National
    KS C IEC 60502-1; KWS 410

Application

Power cable for residential, commercial building and distribution circuit.
The flame retardant cable for tray conformed to the standard of technique of electrical equipment.

Construction

1. Conductor: Annealed copper stranded conductor, Class 2

2. Insulation: Cross-linked Polyethylene (XLPE), Max. operating temperature 90°C.

3. Unit: Cabling circularly insulated solid wire in case of more than 2 cores

4. Outer sheath: Black flame retardant black PVC (TFR PVC)

 

Colors

2 cores: White /Black
3 cores: White / Black /Red,
4 cores: White / Black / Red / Green

Certification

KETI (Safety certification for electrical products)

KWS (Collective standard)

TFR-CV 0.6/1KV design

##image:55978##

 

Construction

Insulation

Filler

Binder tape

Outer sheath (TFR PVC)

  

 

 

 

The values of insulation resistance is not defined but only constant number of insulation resistance is defined
(K=min. 36.7MΩ.km at 90℃)

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Annealed copper
Type of conductor
Stranded, class 2
Insulation
XLPE (Cross-linked Polyethylene)
Outer sheath
PVC
Construction type
Circular compacted strand
Colour
White / Black / Red
With Green/Yellow core
No
With smaller neutral conductor
No

Dimensional characteristics

Dimensional characteristics

Number of cores
3
Conductor cross-section
240 mm²
Conductor diameter
18.3 mm
Average insulation thickness
1.7 mm
Outer Diameter
53.5 mm
Average sheath thickness
2.6 mm
Approximate weight
7580 kg/km
Neutral conductor section (when smaller)
- mm²

Electrical characteristics

Electrical characteristics

Max. DC resistance of the conductor at 20°C
0.0754 Ohm/km
Test voltage
3500 V
Rated Voltage Uo/U (Um)
0,6/1 kV

Usage characteristics

Usage characteristics

Operating temperature, range
-15 ... 60 °C
Flame retardant
KSC IEC 60332-3
Bending factor when installed
12 (xD)

Resources

Resources

Current capacity table XLPE insulation multicore single phase

XLPE or EPR insulation, two loaded conductors/copper or aluminium Conductor temperature: 90 °C, ambient temperature: 30 °C in air, 20 °C in ground
Conductor cross-section
mm² Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
240.0 424.0 338.0 386.0 307.0 459.0 358.0 599.0 439.0 395.0 307.0 448.0 343.0 641.0 470.0
A1 Insulated conductors in conduit in a thermally insulated wall
A2 Multi-core cable in conduit in a thermally insulated wall
B2 Multi-core cable in conduit on a wooden wall
C Single-core or multi-core cable on a wooden wall
D1 Multi-core cable in ducts in the ground
D2 Multi-core cables designed to be buried directly in the ground
E Multi-core cable in free air

Current capacity table XLPE insulation multicore three phase

XLPE or EPR insulation, three loaded conductors/copper or aluminium – Conductor temperature: 90 °C, ambient temperature: 30 °C in air, 20 °C in ground
Conductor cross-section
mm² Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
240.0 380.0 300.0 346.0 273.0 398.0 318.0 500.0 382.0 324.0 253.0 375.0 290.0 538.0 409.0
A1 Insulated conductors in conduit in a thermally insulated wall
A2 Multi-core cable in conduit in a thermally insulated wall
B2 Multi-core cable in conduit on a wooden wall
C Single-core or multi-core cable on a wooden wall
D1 Multi-core cable in ducts in the ground
D2 Multi-core cables designed to be buried directly in the ground
E Multi-core cable in free air

Current capacity table XLPE insulation single core single phase

XLPE or EPR insulation, two loaded conductors/copper or aluminium Conductor temperature: 90 °C, ambient temperature: 30 °C in air, 20 °C in ground
Conductor cross-section
mm² Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
240.0 424.0 338.0 528.0 412.0 599.0 439.0 395.0 307.0 448.0 343.0 679.0 530.0
A1 Insulated conductors in conduit in a thermally insulated wall
B1 Insulated conductors in conduit on a wooden wall
C Single-core or multi-core cable on a wooden wall
D1 Single core or Multi-core cable in ducts in the ground
D2 Single core or Multi-core cables designed to be buried directly in the ground
F Single-core flat cables, touching in free air

Current capacity table XLPE insulation single core three phase

XLPE or EPR insulation, three loaded conductors/copper or aluminium – Conductor temperature: 90 °C, ambient temperature: 30 °C in air, 20 °C in ground
Conductor cross-section
mm² Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
240.0 380.0 300.0 450.0 351.0 500.0 382.0 324.0 253.0 375.0 250.0 634.0 492.0 607.0 471.0
A1 Insulated conductors in conduit in a thermally insulated wall
B1 Insulated conductors in conduit on a wooden wall
C Single-core or multi-core cable on a wooden wall
D1 Single core or Multi-core cable in ducts in the ground
D2 Single core or Multi-core cables designed to be buried directly in the ground
F Single-core flat cables, touching in free air
Ft Single-core trefoil cables, touching in free air

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close