Description
Description
Standards
-
ProductNexans specification
-
NationalKS C IEC 60502-1
Application
Power cable for residential, commercial building and distribution circuit.
The flame retardant cable for tray conformed to the standard of technique of electrical equipment.
Standard
K 60502-1
Nexans standard
Construction
1. Conductor: Annealed copper stranded conductor, Class 2
2. Fire resistant Mica tape.
3. Insulation: Cross-linked polyethylene (XLPE), Max operating temperature: 90°C.
4. Unit: Cabling circularly insulated solid wire in case of more 2 cores
5. Outer sheath: Black flame retardant PVC (TFR-PVC)
Colors
1 core: Natural color
2 cores: White, Black
3 cores: White, Black, Red
4 cores: White, Back, Red, Green
Certification
KETI (Safety certification for electrical products)
TFR-8 0.6/1kV design
##image:56140## |
Conductor Mica tape Insulation Filler Binder tape Outer sheath (TFR PVC) |
The values of insulation resistance is not defined but only constant number of insulation resistance is defined.
(K=min. 36.7MΩ.km at 90℃)
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Dimensional characteristics
Dimensional characteristics
Electrical characteristics
Electrical characteristics
Usage characteristics
Usage characteristics
Resources
Resources
Current capacity table XLPE insulation multicore single phase
XLPE or EPR insulation, two loaded conductors/copper or aluminium Conductor temperature: 90 °C, ambient temperature: 30 °C in air, 20 °C in groundConductor cross-section | ||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
35.0 | 131.0 | 103.0 | 121.0 | 96.0 | 146.0 | 115.0 | 171.0 | 126.0 | 139.0 | 108.0 | 155.0 | 117.0 | 185.0 | 135.0 |
A1 Insulated conductors in conduit in a thermally insulated wall |
A2 Multi-core cable in conduit in a thermally insulated wall |
B2 Multi-core cable in conduit on a wooden wall |
C Single-core or multi-core cable on a wooden wall |
D1 Multi-core cable in ducts in the ground |
D2 Multi-core cables designed to be buried directly in the ground |
E Multi-core cable in free air |
Current capacity table XLPE insulation multicore three phase
XLPE or EPR insulation, three loaded conductors/copper or aluminium – Conductor temperature: 90 °C, ambient temperature: 30 °C in air, 20 °C in groundConductor cross-section | ||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
35.0 | 117.0 | 94.0 | 109.0 | 87.0 | 128.0 | 103.0 | 147.0 | 112.0 | 115.0 | 90.0 | 129.0 | 98.0 | 158.0 | 120.0 |
A1 Insulated conductors in conduit in a thermally insulated wall |
A2 Multi-core cable in conduit in a thermally insulated wall |
B2 Multi-core cable in conduit on a wooden wall |
C Single-core or multi-core cable on a wooden wall |
D1 Multi-core cable in ducts in the ground |
D2 Multi-core cables designed to be buried directly in the ground |
E Multi-core cable in free air |
Current capacity table XLPE insulation single core single phase
XLPE or EPR insulation, two loaded conductors/copper or aluminium Conductor temperature: 90 °C, ambient temperature: 30 °C in air, 20 °C in groundConductor cross-section | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
35.0 | 131.0 | 103.0 | 164.0 | 130.0 | 171.0 | 126.0 | 139.0 | 108.0 | 155.0 | 117.0 | 200.0 | 150.0 |
A1 Insulated conductors in conduit in a thermally insulated wall |
B1 Insulated conductors in conduit on a wooden wall |
C Single-core or multi-core cable on a wooden wall |
D1 Single core or Multi-core cable in ducts in the ground |
D2 Single core or Multi-core cables designed to be buried directly in the ground |
F Single-core flat cables, touching in free air |
Current capacity table XLPE insulation single core three phase
XLPE or EPR insulation, three loaded conductors/copper or aluminium – Conductor temperature: 90 °C, ambient temperature: 30 °C in air, 20 °C in groundConductor cross-section | ||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
35.0 | 117.0 | 94.0 | 144.0 | 116.0 | 147.0 | 112.0 | 115.0 | 90.0 | 129.0 | 82.0 | 176.0 | 135.0 | 169.0 | 129.0 |
A1 Insulated conductors in conduit in a thermally insulated wall |
B1 Insulated conductors in conduit on a wooden wall |
C Single-core or multi-core cable on a wooden wall |
D1 Single core or Multi-core cable in ducts in the ground |
D2 Single core or Multi-core cables designed to be buried directly in the ground |
F Single-core flat cables, touching in free air |
Ft Single-core trefoil cables, touching in free air |
Our websites
Select your country to find our products and solutions
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania