TFR-8 3x 16mm²

Description

Description

Standards

  • Product
    Nexans specification
  • National
    KS C IEC 60502-1

Application

Power cable for residential, commercial building and distribution circuit.
The flame retardant cable for tray conformed to the standard of technique of electrical equipment.

 

Standard

K 60502-1

Nexans standard

 

Construction

1. Conductor: Annealed copper stranded conductor, Class 2

2. Fire resistant Mica tape.

3. Insulation: Cross-linked polyethylene (XLPE), Max operating temperature: 90°C.

4. Unit: Cabling circularly insulated solid wire in case of more 2 cores

5. Outer sheath: Black flame retardant PVC (TFR-PVC)

 

Colors

1 core: Natural color
2 cores: White, Black
3 cores: White, Black, Red
4 cores: White, Back, Red, Green

 

Certification

KETI (Safety certification for electrical products)

TFR-8 0.6/1kV design

##image:56140##

Conductor 

Mica tape 

Insulation 

Filler 

Binder tape 

Outer sheath (TFR PVC)

 

The values of insulation resistance is not defined but only constant number of insulation resistance is defined.
(K=min. 36.7MΩ.km at 90℃)

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Annealed copper
Type of conductor
Stranded, class 2
Construction type
Circular compacted strand
Insulation
Micatape + XLPE
Outer sheath
PVC
Colour
White / Black / Red
With Green/Yellow core
No
With smaller neutral conductor
No

Dimensional characteristics

Dimensional characteristics

Number of cores
3
Conductor cross-section
16 mm²
Conductor diameter
4.7 mm
Average insulation thickness
0.7 mm
Average sheath thickness
1.8 mm
Outer Diameter
22 mm
Approximate weight
650 kg/km
Neutral conductor section (when smaller)
- mm²

Electrical characteristics

Electrical characteristics

Max. DC resistance of the conductor at 20°C
1.15 Ohm/km
Test voltage
3500 V
Rated Voltage Uo/U (Um)
0,6/1 kV

Usage characteristics

Usage characteristics

Operating temperature, range
-15 ... 60 °C
Flame retardant
KSC IEC 60332-3
Bending factor when installed
12 (xD)

Resources

Resources

Current capacity table XLPE insulation multicore single phase

XLPE or EPR insulation, two loaded conductors/copper or aluminium Conductor temperature: 90 °C, ambient temperature: 30 °C in air, 20 °C in ground
Conductor cross-section
mm² Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
16.0 81.0 64.0 76.0 60.0 91.0 72.0 107.0 84.0 91.0 71.0 100.0 76.0 115.0 91.0
A1 Insulated conductors in conduit in a thermally insulated wall
A2 Multi-core cable in conduit in a thermally insulated wall
B2 Multi-core cable in conduit on a wooden wall
C Single-core or multi-core cable on a wooden wall
D1 Multi-core cable in ducts in the ground
D2 Multi-core cables designed to be buried directly in the ground
E Multi-core cable in free air

Current capacity table XLPE insulation multicore three phase

XLPE or EPR insulation, three loaded conductors/copper or aluminium – Conductor temperature: 90 °C, ambient temperature: 30 °C in air, 20 °C in ground
Conductor cross-section
mm² Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
16.0 73.0 58.0 68.0 55.0 80.0 64.0 96.0 76.0 75.0 59.0 84.0 64.0 100.0 77.0
A1 Insulated conductors in conduit in a thermally insulated wall
A2 Multi-core cable in conduit in a thermally insulated wall
B2 Multi-core cable in conduit on a wooden wall
C Single-core or multi-core cable on a wooden wall
D1 Multi-core cable in ducts in the ground
D2 Multi-core cables designed to be buried directly in the ground
E Multi-core cable in free air

Current capacity table XLPE insulation single core single phase

XLPE or EPR insulation, two loaded conductors/copper or aluminium Conductor temperature: 90 °C, ambient temperature: 30 °C in air, 20 °C in ground
Conductor cross-section
mm² Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
16.0 81.0 64.0 100.0 79.0 107.0 84.0 91.0 71.0 100.0 76.0 0.0 0.0
A1 Insulated conductors in conduit in a thermally insulated wall
B1 Insulated conductors in conduit on a wooden wall
C Single-core or multi-core cable on a wooden wall
D1 Single core or Multi-core cable in ducts in the ground
D2 Single core or Multi-core cables designed to be buried directly in the ground
F Single-core flat cables, touching in free air

Current capacity table XLPE insulation single core three phase

XLPE or EPR insulation, three loaded conductors/copper or aluminium – Conductor temperature: 90 °C, ambient temperature: 30 °C in air, 20 °C in ground
Conductor cross-section
mm² Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
16.0 73.0 58.0 88.0 71.0 96.0 76.0 75.0 59.0 84.0 0.0 0.0 0.0 0.0 0.0
A1 Insulated conductors in conduit in a thermally insulated wall
B1 Insulated conductors in conduit on a wooden wall
C Single-core or multi-core cable on a wooden wall
D1 Single core or Multi-core cable in ducts in the ground
D2 Single core or Multi-core cables designed to be buried directly in the ground
F Single-core flat cables, touching in free air
Ft Single-core trefoil cables, touching in free air

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close