NFR-3 stranded 30x2,5mm²
Description
Description
Standards
-
NationalKS C IEC 60502-1; KWS 408
Application
Low-toxic and heat resistant cable for fire alarm in the residential and commerical building.
Construction
- Conductor: Solid conductor (Class 1), Annealed copper stranded conductor, Class 2
- Insulation: Cross-linked polyethylene (XLPE), Max operating temperature: 90°C.
- Unit: Cabling circularly insulated solid conductor in case of more 2 cores
- Outer sheath: Black low-toxic and flame retardant polyefin
Colors
2 cores: White, Black
3 cores: White, Black, Red
4 cores: White, Black, Red, Green
more 5 cores: Numbering on black or red colored core. The other are white.
Certification
KETI, Korea Eco-label
0.6/1kV NFR-3 design
##image:56243## |
Conductor Insulation Filler Binder tape Outer sheath |
The values of insulation resistance is not defined but only constant number of insulation resistance is defined. (K=min. 36.7MΩ.km at room temperature, min. 0.037MΩ.km at 90°C)
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor material
Annealed copper
Type of conductor
Stranded, class 2
Insulation
XLPE
Outer sheath
LSZH
Colour
all cores are black with white numbering
Construction type
7 x 0.67
With Green/Yellow core
No
With smaller neutral conductor
No
Dimensional characteristics
Dimensional characteristics
Number of cores
30
Conductor cross-section
2.5 mm²
Average insulation thickness
0.7 mm
Average sheath thickness
1.8 mm
Outer Diameter
28 mm
Approximate weight
1290 kg/km
Conductor diameter
2.01 mm
Neutral conductor section (when smaller)
- mm²
Electrical characteristics
Electrical characteristics
Max. DC resistance of the conductor at 20°C
7.41 Ohm/km
Test voltage
3500 V
Rated Voltage Uo/U (Um)
0,6/1 kV
Mechanical characteristics
Mechanical characteristics
Corrosivity
IEC 60754-2
Usage characteristics
Usage characteristics
Operating temperature, range
-15 ... 90 °C
Flame retardant
KSC IEC 60332-3
Smoke density
ASTME 662
Bending factor when installed
12 (xD)
Resources
Resources
Current capacity table XLPE insulation multicore single phase
XLPE or EPR insulation, two loaded conductors/copper or aluminium Conductor temperature: 90 °C, ambient temperature: 30 °C in air, 20 °C in groundConductor cross-section | ||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
2.5 | 26.0 | 20.0 | 25.0 | 19.5 | 30.0 | 23.0 | 33.0 | 26.0 | 33.0 | 26.0 | 35.0 | 0.0 | 36.0 | 28.0 |
A1 Insulated conductors in conduit in a thermally insulated wall |
A2 Multi-core cable in conduit in a thermally insulated wall |
B2 Multi-core cable in conduit on a wooden wall |
C Single-core or multi-core cable on a wooden wall |
D1 Multi-core cable in ducts in the ground |
D2 Multi-core cables designed to be buried directly in the ground |
E Multi-core cable in free air |
Current capacity table XLPE insulation multicore three phase
XLPE or EPR insulation, three loaded conductors/copper or aluminium – Conductor temperature: 90 °C, ambient temperature: 30 °C in air, 20 °C in groundConductor cross-section | ||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
2.5 | 23.0 | 19.0 | 22.0 | 18.0 | 26.0 | 21.0 | 30.0 | 24.0 | 28.0 | 22.0 | 30.0 | 0.0 | 32.0 | 24.0 |
A1 Insulated conductors in conduit in a thermally insulated wall |
A2 Multi-core cable in conduit in a thermally insulated wall |
B2 Multi-core cable in conduit on a wooden wall |
C Single-core or multi-core cable on a wooden wall |
D1 Multi-core cable in ducts in the ground |
D2 Multi-core cables designed to be buried directly in the ground |
E Multi-core cable in free air |
Current capacity table XLPE insulation single core single phase
XLPE or EPR insulation, two loaded conductors/copper or aluminium Conductor temperature: 90 °C, ambient temperature: 30 °C in air, 20 °C in groundConductor cross-section | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
2.5 | 26.0 | 20.0 | 31.0 | 25.0 | 33.0 | 26.0 | 33.0 | 26.0 | 35.0 | 0.0 | 0.0 | 0.0 |
A1 Insulated conductors in conduit in a thermally insulated wall |
B1 Insulated conductors in conduit on a wooden wall |
C Single-core or multi-core cable on a wooden wall |
D1 Single core or Multi-core cable in ducts in the ground |
D2 Single core or Multi-core cables designed to be buried directly in the ground |
F Single-core flat cables, touching in free air |
Current capacity table XLPE insulation single core three phase
XLPE or EPR insulation, three loaded conductors/copper or aluminium – Conductor temperature: 90 °C, ambient temperature: 30 °C in air, 20 °C in groundConductor cross-section | ||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
2.5 | 23.0 | 19.0 | 28.0 | 22.0 | 30.0 | 24.0 | 28.0 | 22.0 | 30.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 |
A1 Insulated conductors in conduit in a thermally insulated wall |
B1 Insulated conductors in conduit on a wooden wall |
C Single-core or multi-core cable on a wooden wall |
D1 Single core or Multi-core cable in ducts in the ground |
D2 Single core or Multi-core cables designed to be buried directly in the ground |
F Single-core flat cables, touching in free air |
Ft Single-core trefoil cables, touching in free air |