HFIX solid - 300mm²

Description

Description

Standards

  • Product
    11-SDMS-03, Rev.01; 2014/68/EU
  • National
    KS C 3341

Application

The conductor for the circuits of electrical equipment or instrumentation. Flame retardant and low toxic cross-linked polyefin cable which operates in maximum temperature 90°C.

 

Standard

KS C 3341: Flame retardant and low toxic cross-linked polyefin power cable and insulated wire

 

Construction

1. Conductor: Solid conductor, (Class 1), Annealed copper stranded conductor (Class 2)

2. Insulation: Flame retardant and low toxic XLPO, operating temperature 90°C.

 

Colors

Standard color are black, white, red, green, yellow and blue.

 

HFIX 450/750V design

 ##image:57005##

 

 

Conductor

Insulation

   ##image:57006##

 

 

Conductor

Insulation

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Annealed copper
Insulation
XLPE
Colour
-
Type of conductor
Solid, Class 1
With Green/Yellow core
No
With smaller neutral conductor
No

Dimensional characteristics

Dimensional characteristics

Conductor cross-section
300 mm²
Average insulation thickness
2.4 mm
Minimum outer diameter
24.5 mm
Maximum outer diameter
30.6 mm
Approximate weight
2948 kg/km
Neutral conductor section (when smaller)
- mm²
Number of cores
1

Electrical characteristics

Electrical characteristics

Max. DC resistance of the conductor at 20°C
0.0601 Ohm/km
Test voltage
2500 V
Insulation resistance at 90°C
3.67 MOhm.km
Rated Voltage Uo/U (Um)
450/750 V

Usage characteristics

Usage characteristics

Maximum operating temperature
90 °C

Resources

Resources

Current capacity table XLPE insulation single core single phase

XLPE or EPR insulation, two loaded conductors/copper or aluminium Conductor temperature: 90 °C, ambient temperature: 30 °C in air, 20 °C in ground
Conductor cross-section
mm² Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
300.0 486.0 387.0 603.0 471.0 693.0 508.0 446.0 346.0 502.0 386.0 783.0 613.0
A1 Insulated conductors in conduit in a thermally insulated wall
B1 Insulated conductors in conduit on a wooden wall
C Single-core or multi-core cable on a wooden wall
D1 Single core or Multi-core cable in ducts in the ground
D2 Single core or Multi-core cables designed to be buried directly in the ground
F Single-core flat cables, touching in free air

Current capacity table XLPE insulation single core three phase

XLPE or EPR insulation, three loaded conductors/copper or aluminium – Conductor temperature: 90 °C, ambient temperature: 30 °C in air, 20 °C in ground
Conductor cross-section
mm² Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
300.0 435.0 344.0 514.0 402.0 576.0 440.0 365.0 286.0 419.0 290.0 736.0 571.0 703.0 547.0
A1 Insulated conductors in conduit in a thermally insulated wall
B1 Insulated conductors in conduit on a wooden wall
C Single-core or multi-core cable on a wooden wall
D1 Single core or Multi-core cable in ducts in the ground
D2 Single core or Multi-core cables designed to be buried directly in the ground
F Single-core flat cables, touching in free air
Ft Single-core trefoil cables, touching in free air

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close