HFIX solid - 16mm²
Description
Description
Standards
-
Product11-SDMS-03, Rev.01; 2014/68/EU
-
NationalKS C 3341
Application
The conductor for the circuits of electrical equipment or instrumentation. Flame retardant and low toxic cross-linked polyefin cable which operates in maximum temperature 90°C.
Standard
KS C 3341: Flame retardant and low toxic cross-linked polyefin power cable and insulated wire
Construction
1. Conductor: Solid conductor, (Class 1), Annealed copper stranded conductor (Class 2)
2. Insulation: Flame retardant and low toxic XLPO, operating temperature 90°C.
Colors
Standard color are black, white, red, green, yellow and blue.
HFIX 450/750V design
##image:57005## |
Conductor Insulation |
##image:57006## |
Conductor Insulation |
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor material
Annealed copper
Insulation
XLPE
Colour
-
Type of conductor
Solid, Class 1
With Green/Yellow core
No
With smaller neutral conductor
No
Dimensional characteristics
Dimensional characteristics
Conductor cross-section
16 mm²
Average insulation thickness
1.0 mm
Minimum outer diameter
6.4 mm
Maximum outer diameter
8.0 mm
Approximate weight
167 kg/km
Neutral conductor section (when smaller)
- mm²
Number of cores
1
Electrical characteristics
Electrical characteristics
Max. DC resistance of the conductor at 20°C
1.15 Ohm/km
Test voltage
2500 V
Insulation resistance at 90°C
3.67 MOhm.km
Rated Voltage Uo/U (Um)
450/750 V
Usage characteristics
Usage characteristics
Maximum operating temperature
90 °C
Resources
Resources
Current capacity table XLPE insulation single core single phase
XLPE or EPR insulation, two loaded conductors/copper or aluminium Conductor temperature: 90 °C, ambient temperature: 30 °C in air, 20 °C in groundConductor cross-section | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
16.0 | 81.0 | 64.0 | 100.0 | 79.0 | 107.0 | 84.0 | 91.0 | 71.0 | 100.0 | 76.0 | 0.0 | 0.0 |
A1 Insulated conductors in conduit in a thermally insulated wall |
B1 Insulated conductors in conduit on a wooden wall |
C Single-core or multi-core cable on a wooden wall |
D1 Single core or Multi-core cable in ducts in the ground |
D2 Single core or Multi-core cables designed to be buried directly in the ground |
F Single-core flat cables, touching in free air |
Current capacity table XLPE insulation single core three phase
XLPE or EPR insulation, three loaded conductors/copper or aluminium – Conductor temperature: 90 °C, ambient temperature: 30 °C in air, 20 °C in groundConductor cross-section | ||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
16.0 | 73.0 | 58.0 | 88.0 | 71.0 | 96.0 | 76.0 | 75.0 | 59.0 | 84.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 |
A1 Insulated conductors in conduit in a thermally insulated wall |
B1 Insulated conductors in conduit on a wooden wall |
C Single-core or multi-core cable on a wooden wall |
D1 Single core or Multi-core cable in ducts in the ground |
D2 Single core or Multi-core cables designed to be buried directly in the ground |
F Single-core flat cables, touching in free air |
Ft Single-core trefoil cables, touching in free air |