HFIX solid - 95mm²
HFIX solid - 95mm²
Halogen Free Crosslinked Insulated Wire
450/750V
- Nexans ref. : 14019263
Description
Description
Standards
-
Product11-SDMS-03, Rev.01; 2014/68/EU
-
NationalKS C 3341
Application
The conductor for the circuits of electrical equipment or instrumentation. Flame retardant and low toxic cross-linked polyefin cable which operates in maximum temperature 90°C.
Standard
KS C 3341: Flame retardant and low toxic cross-linked polyefin power cable and insulated wire
Construction
1. Conductor: Solid conductor, (Class 1), Annealed copper stranded conductor (Class 2)
2. Insulation: Flame retardant and low toxic XLPO, operating temperature 90°C.
Colors
Standard color are black, white, red, green, yellow and blue.
HFIX 450/750V design
##image:57005## |
Conductor Insulation |
##image:57006## |
Conductor Insulation |
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor material
Annealed copper
Insulation
XLPE
Colour
-
Type of conductor
Solid, Class 1
With Green/Yellow core
No
With smaller neutral conductor
No
Dimensional characteristics
Dimensional characteristics
Conductor cross-section
95 mm²
Average insulation thickness
1.6 mm
Minimum outer diameter
14.1 mm
Maximum outer diameter
17.6 mm
Approximate weight
933 kg/km
Neutral conductor section (when smaller)
- mm²
Number of cores
1
Electrical characteristics
Electrical characteristics
Max. DC resistance of the conductor at 20°C
0.193 Ohm/km
Test voltage
2500 V
Insulation resistance at 90°C
3.67 MOhm.km
Rated Voltage Uo/U (Um)
450/750 V
Usage characteristics
Usage characteristics
Maximum operating temperature
90 °C
Resources
Resources
Current capacity table XLPE insulation single core single phase
XLPE or EPR insulation, two loaded conductors/copper or aluminium Conductor temperature: 90 °C, ambient temperature: 30 °C in air, 20 °C in groundConductor cross-section | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
95.0 | 241.0 | 191.0 | 306.0 | 242.0 | 328.0 | 241.0 | 239.0 | 186.0 | 270.0 | 204.0 | 377.0 | 289.0 |
A1 Insulated conductors in conduit in a thermally insulated wall |
B1 Insulated conductors in conduit on a wooden wall |
C Single-core or multi-core cable on a wooden wall |
D1 Single core or Multi-core cable in ducts in the ground |
D2 Single core or Multi-core cables designed to be buried directly in the ground |
F Single-core flat cables, touching in free air |
Current capacity table XLPE insulation single core three phase
XLPE or EPR insulation, three loaded conductors/copper or aluminium – Conductor temperature: 90 °C, ambient temperature: 30 °C in air, 20 °C in groundConductor cross-section | ||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
95.0 | 216.0 | 171.0 | 269.0 | 217.0 | 278.0 | 211.0 | 197.0 | 154.0 | 226.0 | 144.0 | 342.0 | 264.0 | 328.0 | 253.0 |
A1 Insulated conductors in conduit in a thermally insulated wall |
B1 Insulated conductors in conduit on a wooden wall |
C Single-core or multi-core cable on a wooden wall |
D1 Single core or Multi-core cable in ducts in the ground |
D2 Single core or Multi-core cables designed to be buried directly in the ground |
F Single-core flat cables, touching in free air |
Ft Single-core trefoil cables, touching in free air |